A Failure Case of Level Switch/transmitter that controls a solenoid operated valve
May 28, 2024
Here is a failure case that the level switch tripped and the valve closed when the Level was still above the setted lower level point. The level switch is supposed to trip when level gets lower than the setted point and have the valve close.
This failure would happen when vessel vapor temperature is higher than the minimum ambient. If so, the vapor leg should be remote sealed to prevent saturated vapor from getting into the vapor leg of the level transmitter.